| Item | Specifications |
|---|---|
| Model | NFDR541-T |
| Number of output channels | 16 |
| Rated applied voltage | 24 to 125 V DC (*5) 100 to 240 V AC, 50/60 Hz |
| Maximum load current (*2) | Resistive load: 2.0 A/channel at 24 V DC 1.0 A/channel at 48 V DC 0.3 A/channel at 110 V DC 0.3 A/channel at 125 V DC 2.0 A/channel at 100 V AC 2.0 A/channel at 220 V AC Inductive load: 0.6 A/channel at 24 V DC 0.3 A/channel at 48 V DC 0.1 A/channel at 110 V DC 2.0 A/channel at 100 V AC 1.0 A/channel at 220 V AC |
| Withstanding voltage | Between output signal and system: 2000 V AC for 1 minute Between commons: 1350 V AC for 1 minute, common every 8-channel |
| Functions Status output |
ON/OFF status output function |
| Output fallback (*3) (*4) | HOLD: Holds the current states when the fallback action is triggered. OFF: Resets all the output channels to off when the fallback action is triggered. NO: Performs no fallback action. |
| Output response time | 12 ms or less (for status output) |
| Maximum current consumption | 780 mA (5 V DC) |
| Weight | 0.3 kg |
| External connection | Pressure clamp terminal |