•  ALF111 Yokogawa Foundation Fieldbus Communication Module
  •  ALF111 Yokogawa Foundation Fieldbus Communication Module

 ALF111 Yokogawa Foundation Fieldbus Communication Module

 ALF111 Yokogawa Foundation Fieldbus Communication Module Foundation Fieldbus Communication Module 
This document describes the hardware specifications of the ALF111 Foundation Fieldbus communication module, which is to be installed in Node Unit for ESB Bus (ANB10S or ANB10D), Node Unit for ER Bus (ANR10S or ANR10D), Compact Field Control Unit (for FIO) (AFF50S or AFF50D) and Compact Field Control Unit (for Vnet/IP, for FIO) (AFV10S or AFV10D) when used
Manufacturer:
YOKOGAWA
Model:
ALF111
  •  ALF111 Yokogawa Foundation Fieldbus Communication Module

Description

 ALF111 Yokogawa Foundation Fieldbus Communication Module

This document describes the hardware specifications of the ALF111 Foundation Fieldbus communication module, which is to be installed in Node Unit for ESB Bus (ANB10S or ANB10D), Node Unit for ER Bus (ANR10S or ANR10D), Compact Field Control Unit (for FIO) (AFF50S or AFF50D) and Compact Field Control Unit (for Vnet/IP, for FIO) (AFV10S or AFV10D) when used 

 STANDARD SPECIFICATIONS

ALF111 Module

An ALF111 works as the Link Active Scheduler (LAS) of FOUNDATION fieldbus (H1) and transfers data from/to field devices for FOUNDATION fieldbus.

Interfaces

FOUNDATION fieldbus (Low speed Voltage Mode) 4 ports (one port is connected to one segment)

Transmission Speed

31.25 kbps

Function

LAS (needs to be prepared a MTL5995 (fieldbus power supply)).

Specifications for Fieldbus Device Connections

See General Specifications - Model LFS2610,Foundation Fieldbus Communication Package (for ALF111)

Current consumption

0.5 A or less

Withstanding Voltage

Field-to-system: 1500 V AC for 1 minute

Bus Connections (external connections)

Can be chosen from the followings:
• Pressure clamp terminals (removable terminal block with built-in terminators that can be switched on/off)
• Connecting to a terminal board using AKB336 (the YCB138 terminators are mounted on the terminal board).

Installation

To be installed in an ANB10S, ANB10D, ANR10S,ANR10D, AFF50S, AFF50D, AFV10S or AFV10D nest.

Weight

0.4 kg 